Quick Answer: Electric tankless water heaters draw far more amperage than most homeowners expect, because unlike gas units they use electricity for all of the heating, not just ignition. A small 8 kW point-of-use unit like the EcoSmart ECO 8 draws 33 amps on a single 40-amp double-pole breaker, an 18 kW unit like the Rheem RTEX-18 draws 75 amps on two 40-amp breakers, and a flagship 36 kW whole-home unit like the Rheem RTEX-36 draws up to 150 amps split across four separate 40-amp double-pole breakers on 8 AWG wire, per EcoSmart’s and Rheem’s spec sheets. Rheem recommends a 150-amp home service for its 18 kW model, 200 amps for 24 to 27 kW and 300 amps for 36 kW, and Stiebel Eltron’s own installation guidance recommends a minimum 150-amp home electrical service for a 24kW unit and 300 amps for a 36kW unit — which is why many electric tankless installs also require a panel upgrade or dedicated subpanel, not just a new breaker.

Last updated November 11, 2026: corrected the EcoSmart rows, which had each model’s amp draw and breakers shifted one size up (the ECO 11 is 13 kW and 54 A, not 18 kW and 33 A; the ECO 18 is 18 kW and 75 A on two 40-amp breakers, not 24 kW on one 60-amp breaker), against EcoSmart’s product pages; added the Rheem RTEX-13, RTEX-18 and RTEX-27 from Rheem’s spec sheet and installation manual; and corrected the claim that maker breaker sizes always include a 125% margin.

Every brand roundup on this site compares GPM and BTU, but the number that actually decides whether an electric tankless heater is a straightforward DIY-adjacent swap or a full electrical-service project is amperage. A gas tankless unit only needs a standard 120V outlet for its control board; an electric tankless unit uses its 240V circuit to generate every bit of heat, which is why the amp draw scales so much faster with output.

Why electric tankless amp draw is so much higher than it looks

An electric tankless heater is close to 99% efficient at the point of use — almost none of the electrical energy is lost to venting or standby loss, unlike a gas unit. But that same efficiency means every watt of heating comes directly off the circuit, with no combustion doing part of the work. A 36kW unit is drawing 36,000 watts continuously while it’s running, and at 240V that works out to 150 amps — more than the entire main service in many older homes.

ModelRatingAmp draw (240V)Breaker(s)Wire gauge
EcoSmart ECO 88 kW33 A1 × 40A DP1 × 8 AWG
EcoSmart ECO 1113 kW54 A1 × 60A DP1 × 6 AWG
Rheem RTEX-1313 kW54 A1 × 60A DP1 × 6 AWG
EcoSmart ECO 1818 kW75 A2 × 40A DP2 × 8 AWG
Rheem RTEX-1818 kW75 A2 × 40A DP2 × 8 AWG
Stiebel Eltron Tempra 24 Plus24 kW100 A2 × 50A DP2 × 6 AWG
Rheem RTEX-2424 kW100 A3 × 40A DP3 × 8 AWG
EcoSmart ECO 2727 kW113 A3 × 40A DP3 × 8 AWG
Rheem RTEX-2727 kW113 A3 × 40A DP3 × 8 AWG
EcoSmart ECO 3636 kW150 A4 × 40A DP4 × 8 AWG
Stiebel Eltron Tempra 36 Plus36 kW150 A3 × 50A DP3 × 6 AWG
Rheem RTEX-3636 kW150 A4 × 40A DP4 × 8 AWG

EcoSmart rows checked against EcoSmart’s product pages and Rheem rows against Rheem’s RTEX spec sheet (RH-TE-WH-SS Rev. 1), selling guide (TKE-401 Rev. 5) and installation manual on November 11, 2026; Stiebel Eltron rows from Stiebel’s installation documents (Tempra 36 Plus re-checked October 17, 2026). Always confirm against the exact manual for your specific model — manufacturers revise breaker counts between revisions, and local code can require different sizing.

Notice that EcoSmart and Rheem, both Rheem-owned brands, list identical breaker counts at each kW size: up to 13 kW on one breaker, then one 40-amp circuit per element above that (Rheem’s manual lists two 9 kW elements in the 18 kW model). Stiebel Eltron splits the same 24 kW differently, on two 50-amp breakers with 6 AWG wire instead of three 40-amp breakers with 8 AWG. Neither approach is wrong, but it means you can’t reuse a breaker count from one brand’s 24 kW model when installing a different brand’s 24 kW model. Our Rheem RTEX-18 review shows how much hot water the 75-amp, 18 kW size delivers by groundwater zone. See our best electric tankless water heater picks for the full spec sheet on each model before assuming the electrical requirements match.

The NEC’s 125% continuous-load rule

The National Electrical Code defines a continuous load as one whose maximum current is expected to last 3 hours or more, and sizes those circuits at 125% of the load. Its water-heater rule (section 422.13) applies that automatically to fixed storage-type heaters of 120 gallons or less; how an inspector treats a tankless unit, which only draws full power while hot water is flowing, varies by jurisdiction. Under a 125% rule, a 100-amp heater becomes a 125-amp calculated load.

Don’t assume the maker’s breaker size already includes that margin. Rheem and EcoSmart list two 40-amp breakers for a 75-amp, 18 kW heater, which is 37.5 amps on each 40-amp circuit, about 94% of the breaker rating rather than 80%. Rheem’s installation manual says all wiring must meet the NEC and notes that the Canadian Electrical Code generally requires circuits sized to 125% of the heater’s maximum current. Ask your electrician which rule your inspector applies before buying breakers and wire.

Multi-circuit units complicate this further: each of the two to four double-pole breakers on a flagship unit is sized and wired as its own independent 125%-rated circuit, landing at its own terminal pair inside the heater. Skipping a circuit, undersizing one leg, or sharing a neutral between circuits is a common installation mistake that either trips breakers under full load or — worse — creates a fire risk that won’t show up until the unit is drawing its full rated amperage on a cold morning.

When you need a panel upgrade or subpanel

UnitManufacturer's minimum home service
Rheem RTEX-18 / EcoSmart ECO 18 (18 kW)150 amp
Rheem RTEX-24 / RTEX-27, EcoSmart ECO 27 (24 to 27 kW)200 amp
Rheem RTEX-36 / EcoSmart ECO 36 (36 kW)300 amp
Stiebel Eltron Tempra 24 Plus (24 kW)150 amp
Stiebel Eltron Tempra 29 Plus (28.8 kW)200 amp
Stiebel Eltron Tempra 36 Plus (36 kW)300 amp

Many homes built before the 1990s still run 100-amp or 125-amp main service — enough for lighting, HVAC, and standard appliances, but nowhere near enough headroom to add a flagship electric tankless unit on top. Stiebel Eltron’s own installation guidance is explicit about this: a 36kW Tempra 36 Plus assumes at least 300 amps of total home service, nearly double what many houses have. If your panel is already close to its labeled capacity from existing loads (central AC, an EV charger, an electric range), a licensed electrician needs to run a full load calculation, not just check for open breaker slots.

Even when the main service has enough headroom, most panels don’t have two to four open double-pole slots sitting unused — which is why many installs add a small subpanel dedicated to the water heater rather than trying to free up slots in an already-full main panel. Some local codes also require a disconnect within sight of the unit, which a subpanel satisfies automatically if it’s mounted near the heater.

6 AWG THHN Copper Building Wire (Per Foot / Spool)

Matches the wire gauge most 24–36kW electric tankless circuits call for · check your model's exact gauge before buying
  • 6 AWG copper is the wire gauge specified for the 13 kW EcoSmart ECO 11 and Rheem RTEX-13 single circuits and the Stiebel Eltron Tempra Plus double-pole circuits listed above. EcoSmart and Rheem models from 18 kW up call for 8 AWG on each of two to four 40-amp circuits instead, so confirm your model's manual before purchasing.
  • THHN/THWN-2 insulation is rated for both dry and wet locations, which matters if any part of the run passes through an unconditioned space like a garage or crawlspace.
  • Buy per the exact run length needed for each circuit — this is licensed-electrician work on anything beyond a single-circuit point-of-use unit, given the double-pole breaker count involved.
Check price on eBay →

Double-Pole 40/50/60A Circuit Breaker (Panel-Matched)

Matches the breaker sizes most electric tankless models call for · confirm brand/model compatibility with your panel first
  • Breaker compatibility is panel-brand-specific — a double-pole breaker rated correctly in amps still won't fit or won't be code-legal in a panel it isn't classified for, so match the panel manufacturer before ordering.
  • Multi-circuit units (24kW and up) need two to four of these, each landing its own conductor pair — buy the exact count your model's manual specifies, not one per unit.
  • Breaker installation inside a live panel is licensed-electrician work in most jurisdictions and is required for the installation to pass inspection.
Check price on eBay →

120/240V Load Center Subpanel (8–12 Circuit)

Best when your main panel has fewer open double-pole slots than your unit needs
  • A dedicated subpanel near the water heater location solves both the open-slot problem and, in many jurisdictions, the code requirement for a disconnect within sight of the unit.
  • Sized well beyond a single tankless heater's circuit count so it has room for the required number of double-pole breakers without crowding a shared panel with unrelated circuits.
  • Subpanel feed sizing, grounding, and bonding must still be calculated by a licensed electrician against your specific unit's total amp draw — this is not a DIY panel swap.
Check price on eBay →

How to choose

The bottom line

Electric tankless water heaters trade gas-line and venting work for amperage, and the amperage adds up fast: a small 8 kW unit draws 33 amps on one breaker, an 18 kW unit draws 75 amps on two, and a flagship 36 kW whole-home unit can draw up to 150 amps split across three or four separate double-pole breakers. Your electrician sizes the breakers and wire from that draw and from whether your inspector applies a 125% margin, and manufacturers publish minimum home-service recommendations — Rheem lists 150 amps for its 18 kW model and 300 amps for 36 kW, Stiebel Eltron 150 amps for a 24 kW unit and 300 amps for 36 kW — that many older homes simply don’t have without a panel upgrade or dedicated subpanel. Get your model’s exact breaker count, wire gauge, and minimum service size from its own installation manual before you buy, and have a licensed electrician confirm your panel has the headroom before the heater arrives.

Previous update 2026-10-17: re-verified the flagship breaker and wire figures against current source documents. Rheem’s own RTEX-36 spec sheet confirms 150A at 240V across four 40A double-pole breakers on 8 AWG wire — unchanged. Stiebel Eltron’s own sizing guide confirms the Tempra 36 Plus at 150A draw, a 300A minimum home service, and three separate 50A double-pole breakers on 6-gauge copper — also unchanged, despite at least one third-party retailer listing circulating an inconsistent 60A breaker figure for the same model. If you see a breaker count that doesn’t match the table above, check it against the manufacturer’s own current sizing guide rather than a retailer listing.